首页 | 本学科首页   官方微博 | 高级检索  
     

基于Teager能量算子瞬时能量的贯通式同相自耦变压器牵引供电系统牵引网纵联保护方案
引用本文:王龙,蔡潇,高敬业,蔡旺,毕贵红,陈仕龙. 基于Teager能量算子瞬时能量的贯通式同相自耦变压器牵引供电系统牵引网纵联保护方案[J]. 科学技术与工程, 2021, 21(32): 13728-13736
作者姓名:王龙  蔡潇  高敬业  蔡旺  毕贵红  陈仕龙
作者单位:昆明理工大学电力工程学院, 昆明650500;云南电网有限责任公司电力科学研究院, 昆明650217;昆明理工大学电力工程学院, 昆明650500
基金项目:国家自然科学基金项目(面上项目,重点项目,重大项目);贯通式同相供电高速铁路牵引网馈线行波保护研究
摘    要:提出一种基于Teager能量算子瞬时能量的贯通式同相AT牵引供电系统牵引网纵联保护方案。牵引变电所出口并联电容与一段接触线构成牵引网边界,通过分析发现该边界对高频信号有很强的衰减所用。利用FEEMD分解提取故障电流高频分量,然后利用Teager能量算子计算故障电流高频分量的瞬时能量,并提取两端瞬时能量最大值。区外故障时,故障电流高频分量瞬时能量最大值较小;区内故障时,该值较大。根据该差异来构造保护动作判据,判别故障位置,决定保护是否动作。基于PSCAD大量仿真实验表明,该保护方案能够准确判别区内、外故障,并且有较好的耐过渡电阻能力。

关 键 词:贯通式同相自耦变压器(AT)供电系统  牵引网  快速集合经验模态分解(FEEMD)  Teager能量算子  纵联保护
收稿时间:2021-04-06
修稿时间:2021-10-29

Pilot protection scheme of traction network based on Teager energy operator transient energy for continuous co-phase AT power supply system
Wang Long,Cai Xiao,Gao Jingye,Cai Wang,Bi Guihong,Chen Shilong. Pilot protection scheme of traction network based on Teager energy operator transient energy for continuous co-phase AT power supply system[J]. Science Technology and Engineering, 2021, 21(32): 13728-13736
Authors:Wang Long  Cai Xiao  Gao Jingye  Cai Wang  Bi Guihong  Chen Shilong
Affiliation:School of Electric Power Engineering,Kunming University of Science and Technology
Abstract:A traction network longitudinal protection scheme based on FEEMD and Teager energy operator transient energy for continuous co-phase AT power supply system is proposed. The traction substation outlet shunt capacitor and a section of contact line constitute the traction network boundary, which is found to have a strong attenuation used for high-frequency signals through analysis. Therefore, the FEEMD decomposition is used to extract the high-frequency component of the fault current, and then the Teager energy operator is used to calculate the instantaneous energy of the high-frequency component of the fault current and extract the maximum instantaneous energy at both ends. In the case of faults outside the zone, the maximum value of the instantaneous energy of the high-frequency component of the fault current is smaller; in the case of faults inside the zone, the value is larger. The difference is used to construct the protection action criterion to identify the fault location and decide whether the protection will operate. Large amount of simulation results based on PSCAD indicate that the protection scheme can accurately discriminate internal and external faults and has good resistance to transition resistance.
Keywords:continuous co-phase AT power supply system   traction network   FEEMD   Teager energy operator   pilot protection
本文献已被 万方数据 等数据库收录!
点击此处可从《科学技术与工程》浏览原始摘要信息
点击此处可从《科学技术与工程》下载全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号