Influence of Thermal Flow Field of Cooling Tower on Recirculation Ratio of a Direct Air-Cooled System for a Power Plant
作者姓名:赵万里
作者单位:北京航空航天大学
摘    要:In order to get thermal flow field of direct air-cooled system, the hot water was supplied to the model of direct air-cooled condenser(ACC). The particle image velocimetery (PIV) experiments were carried out to get thermal flow field of a ACC under different conditions in low velocity wind tunnel, at the same time, the recirculation ratio at cooling tower was measured, so the relationship between flow field characteristics and recirculation ratio of cooling tower can be discussed. From the results we can see that the flow field configuration around cooling tower has great effects on average recirculation ratio under cooling tower. The eddy formed around cooling tower is a key reason that recirculation produces. The eddy intensity relates to velocity magnitude and direction angle, and the configuration of eddy lies on the geometry size of cooling tower. So changing the flow field configuration around cooling tower reasonably can decrease recirculation ratio under cooling tower, and heat dispel effect of ACC can also be improved.

关 键 词:直接空冷系统  冷却塔  流量场  再循环  电厂  比例  流场特性  冷却冷凝器
收稿时间:4/1/2008 12:22:34 PM
修稿时间:4/13/2008 4:51:36 PM

Influence of Thermal Flow Field of Cooling Tower on Recirculation Ratio of a Direct Air-Cooled System for a Power Plant
zhao wanli.Influence of Thermal Flow Field of Cooling Tower on Recirculation Ratio of a Direct Air-Cooled System for a Power Plant[J].Engineering Sciences,2008,6(4):64-70.
Authors:zhao wanli
Institution:Beijing University of Aeronautics and Astronauts
Abstract:In order to get thermal flow field of direct air-cooled system, the hot water was supplied to the direct air-cooled condenser. The PIV experiments were carried out to get thermal flow field of a direct air-cooled system under different conditions in low velocity wind tunnel, at the same time, the recirculation ratio at cooling tower was measured, so the relationship between flow field characteristic and recirculation ratio of cooling tower can be discussed, from the results we can see that: the flow field configuration fore-and-aft cooling tower has great effects on average recirculation ratio under cooling tower. The eddy formed fore-and-aft cooling tower is a key reason that recirculation produces. The eddy intensity relates to velocity magnitude and direction angle, the configuration of eddy lies on the geometry size of cooling tower. So changing the flow field configuration fore-and-aft cooling tower reasonably can decrease recirculation ratio under cooling tower, and heat dispel effect of ACC can also be improved.
Keywords:Power Plant  Direct Air-Cooled Condenser  Thermal Flow Field Characteristics    Recirculation Ratio  PIV Experiment