Partial Discharge Characteristics in the Course of Aging within XLPE Insulation
作者姓名:WANG  Hongxin  CHENG  Shukang  WEN  Xishan  FU  Duan
作者单位:[1]School of Electrical Engineering, Wuhan University, Wuhan 430072, Hubei, China [2]School of Electrical Engineering and Automation, Harbin Institute of Technology, Harbin 150001, Heilongjiang, China
基金项目:Supported by the National Natural Science Foundation of China (59677018)
摘    要:This paper deals with the experimental study on the correlation between partial discharge (PD) characteristic parameters and corresponding aging degree of insulation in the course of the aging within eros,s-linked polyethylene (XLPE) insulation. The aging tests were performed on a section of 10 kV transmission cable by means of water needle method. The PD macroscopic characteristic parameters were found to be significantly dependent on the corresponding aging degree of insulation in the course of aging of XLPE, and different kind of aging stage has different characteristics. Beside, there are similar regularity but different PD amplitude in the course of aging of XI.PE insulation in different electrolyte, and their insulation life is different. Therefore, according to the chan ging regularity of the PD macroscopic characteristic parame ters within XLPE insulation judging the aging degree of XLPE insulation will be an effective method.

关 键 词:聚乙烯  老化  部分放电  实验研究  XLPE  绝缘
文章编号:1007-1202(2006)02-0389-05
收稿时间:2005-04-20

Partial discharge characteristics in the course of aging within XLPE insulation
WANG Hongxin CHENG Shukang WEN Xishan FU Duan.Partial Discharge Characteristics in the Course of Aging within XLPE Insulation[J].Wuhan University Journal of Natural Sciences,2006,11(2):389-393.
Authors:Wang Hongxin  Cheng Shukang  Wen Xishan  Fu Duan
Institution:(1) School of Electrical Engineering, Wuhan University, 430072 Wuhan, Hubei, China;(2) School of Electrical Engineering and Automation, Harbin Institute of Technology, 150001 Harbin, Heilongjiang, China
Abstract:This paper deals with the experimental study on the correlation between partial discharge (PD) characteristic parameters and corresponding aging degree of insulation in the course of the aging within cross-linked polyethylene (XLPE) insulation. The aging tests were performed on a section of 10 kV transmission cable by means of water needle method. The PD macroscopic characteristic parameters were found to be significantly dependent on the corresponding aging degree of insulation in the course of aging of XLPE, and different kind of aging stage has different characteristics. Beside, there are similar regularity but different PD amplitude in the course of aging of XLPE insulation in different electrolyte, and their insulation life is different. Therefore, according to the changing regularity of the PD macroscopic characteristic parameters within XLPE insulation judging the aging degree of XLPE insulation will be an effective method.
Keywords:cross-linked polyethylene  aging  partial discharge