CO2热泵热水器充注量确定及系统实验研究
引用本文:刘业凤,朱洪亮,张峰,卓之阳.CO2热泵热水器充注量确定及系统实验研究[J].上海理工大学学报,2015,37(1):49-56.
作者姓名:刘业凤  朱洪亮  张峰  卓之阳
作者单位:上海理工大学 能源与动力工程学院, 上海 200093;上海理工大学 能源与动力工程学院, 上海 200093;上海理工大学 能源与动力工程学院, 上海 200093;上海理工大学 能源与动力工程学院, 上海 200093
摘    要:设计搭建蒸发器和气冷器均采用套管式换热器的跨临界CO2热泵热水器性能测试实验台,采用额定工况法理论计算系统充注量,实验研究充注量对系统性能的影响并确定系统最佳充注量.在最佳充注量下,实验研究节流阀开度和气冷器水流量的变化对系统性能的影响.结果表明,充注量的变化对排气压力、性能系数COP影响最大,对蒸发压力影响很小;节流阀开度过小会提高系统高压压力,增加系统能耗,而对产热水温度提升不大;只有气冷器水流量适中时,系统才能在较高的COP时提供温度满足使用要求的热水.

关 键 词:二氧化碳  制冷剂充注量  跨临界循环  热泵热水器  实验研究
收稿时间:2013/12/12 0:00:00

Determining the Refrigerant Charging Amount and Experimental Study on CO2 Heat Pump Water Heater
LIU Yefeng,ZHU Hongliang,ZHANG Feng and ZHUO Zhiyang.Determining the Refrigerant Charging Amount and Experimental Study on CO2 Heat Pump Water Heater[J].Journal of University of Shanghai For Science and Technology,2015,37(1):49-56.
Authors:LIU Yefeng  ZHU Hongliang  ZHANG Feng and ZHUO Zhiyang
Institution:School of Energy and Power Engineering, University of Shanghai for Science and Technology, Shanghai 200093, China;School of Energy and Power Engineering, University of Shanghai for Science and Technology, Shanghai 200093, China;School of Energy and Power Engineering, University of Shanghai for Science and Technology, Shanghai 200093, China;School of Energy and Power Engineering, University of Shanghai for Science and Technology, Shanghai 200093, China
Abstract:A performance testing platform for heat pump water heater of CO2 trans-critical cycle was designed and then constructed.Its evaporator and gas cooler were both sleeve type heat exchanger.The optimum charging amount was determined through experimental study.With the optimum charging amount, the effects of throttle opening degree and gas cooler water flow on the performance of the system were studied experimentally.The results show that the change of charging amount has more influence on discharge pressure and COP (coefficient of performance) of the system, and its influence on the evaporation pressure is rather small.If the throttle opening degree is too small, the discharge pressure and energy consumption of the system will be increased rapidly.Only when the water flow of gas cooler is appropriate, the system can provide hot water to meet the requirements with higher COP.
Keywords:carbon dioxide  refrigerant charge amount  trans-critical cycle  heat pump water heater  experimental study
本文献已被 CNKI 万方数据 等数据库收录!
点击此处可从《上海理工大学学报》浏览原始摘要信息
点击此处可从《上海理工大学学报》下载免费的PDF全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏