首页 | 本学科首页   官方微博 | 高级检索  
     检索      

一起110kV复合套管充油终端故障分析及对策
引用本文:陈腾彪,邬韬,曾南华,王炼兵,魏前虎.一起110kV复合套管充油终端故障分析及对策[J].科技信息,2012(11):442-443.
作者姓名:陈腾彪  邬韬  曾南华  王炼兵  魏前虎
作者单位:深圳供电局有限公司,广东深圳518020
摘    要:通过对一起发生故障的110kV电缆线路户外电缆终端进行解剖,分析认为造成故障的主要原因是应力锥与电缆表面界面压力不足及电缆绝缘表面处理可能存在缺陷,并提出防止该类故障的对策。

关 键 词:充油  电缆终端  故障分析

110kV Composite Bushing Oil Terminal Fault Analysis and Countermeasures
CHEN Teng-biao,WU Tao,ZENG Nan-hua,WANG Lian-bing,WEI Qian-hu.110kV Composite Bushing Oil Terminal Fault Analysis and Countermeasures[J].Science,2012(11):442-443.
Authors:CHEN Teng-biao  WU Tao  ZENG Nan-hua  WANG Lian-bing  WEI Qian-hu
Institution:(Shenzhen Power Supply Bureau CO.,LTD.,Shenzhen Guangdong,518020,China)
Abstract:Based on the fault of 110kV cable line outdoor cable terminal were dissected,analysis the main reasons of causing faults is a stress cone and cable surface interface pressure is insufficient and cable insulation surface treatment may be put in blemish,put forward to prevent the fault countermeasures.
Keywords:Oil-filled  Cable terminal  Fault analyzing
本文献已被 维普 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号