变电站软母线下料长度二分法数值计算模型
引用本文:黄宴委,王庭桉.变电站软母线下料长度二分法数值计算模型[J].福州大学学报(自然科学版),2016,44(6):767-773.
作者姓名:黄宴委  王庭桉
作者单位:福州大学电气工程与自动化学院,福建 福州 350116,福州大学电气工程与自动化学院,福建 福州 350116
基金项目:福建省自然科学基金资助项目(面上项目,重点项目,重大项目)
摘    要:针对变电站软母线的下料长度问题,提出一种二分法的数值求解模型.首先在假设水平应力已知的条件下,由受力分析建立软母线下料长度的非线性耦合解析模型,进而设计变电站软母线下料长度二分法数值计算模型,并利用二分法得到精确的数值解.仿真与应用结果表明,数值计算模型能够得到非常准确的下料长度,安装后的软导线总弧垂误差均在-2%~+3%以内,具有良好的施工效果.

关 键 词:变电站  软母线  下料长度  非线性耦合模型  数值模型  二分法

The dichotomy numerical calculation model of soft-bus conductor length in transformer substation
HUANG Yanwei and WANG Tingan.The dichotomy numerical calculation model of soft-bus conductor length in transformer substation[J].Journal of Fuzhou University(Natural Science Edition),2016,44(6):767-773.
Authors:HUANG Yanwei and WANG Tingan
Institution:College of Electrical Engineering Automation,Fuzhou University,Fuzhou,College of Electrical Engineering Automation,Fuzhou University,Fuzhou
Abstract:The soft-bus conductor in transformer substation is a kind of short-distance overhead lines, and its cutting length is directly affected by length and weight of the tension insulator string. Under the assumption of that the horizontal stress is known, this article establishes a nonlinear coupling analytical model of soft-bus conductor length through stress analysis. Furthermore, it designs a numerical calculation of soft-bus conductor length in transformer substation. Given the sag, the numerical calculation consists of five modules, namely the dichotomy adjustment of sag step, the horizontal stress calculation and adjustment, the projection length calculation, the adjustment for calculation error of total sag, and the calculation of soft-bus conductor length. Then the numerical calculation obtains accurate numerical solution through dichotomy. It is demonstrated by the result of simulation and application that an accurate soft-bus conductor length can be worked out through the numerical calculation method. Besides, the total sag error of soft wire after installation is between -2% to 3% so that the construction effect will be satisfactory.
Keywords:transformer substation  soft-bus conductor  cutting length  nonlinear coupling  numerical calculation  dichotomy
本文献已被 CNKI 等数据库收录!
点击此处可从《福州大学学报(自然科学版)》浏览原始摘要信息