Experimental study on CO2/CO of typical lining materials in full-scale fire test
引用本文:WANG Wei ZHANG HePing WAN YuTian. Experimental study on CO2/CO of typical lining materials in full-scale fire test[J]. 科学通报(英文版), 2007, 52(9): 1282-1286. DOI: 10.1007/s11434-007-0151-y
作者姓名:WANG Wei ZHANG HePing WAN YuTian
作者单位:State Key Laboratory of Fire Science, University of Science and Technology of China, Hefei 230027, China
基金项目:Supported by the National Natural Science Foundation of China (Grant No. 50323005) and the National Basic Research Program of China (Grant No. 2001 CB409603 )
摘    要:Lining materials are widely used in buildings to cover walls and ceilings. Combustible linings may produce a potential high fire hazard in buildings. Once ignited, it propagates fire and accelerates the enclosure fire growth. Two types of lining materials were studied during the tests: block board and plywood. The test was conducted in an ISO 9705 room, where linings were mounted on walls without the ceiling. By changing the heat output of the burner, the ventilation, etc., the concentrations of CO2/CO of different lining materials were researched. The effect of test conditions on the production of CO2/CO of different lining materials was investigated, and useful experimental data were provided for the further development of numerical modeling to simulate enclosure fire growth lined with combustible materials.

关 键 词:典型装饰材料  足尺火灾试验  CO2  CO  有害气体  实验研究
收稿时间:2006-09-13
修稿时间:2006-09-132007-01-23

Experimental study on CO2/CO of typical lining materials in full-scale fire test
Wang Wei,Zhang HePing,Wan YuTian. Experimental study on CO2/CO of typical lining materials in full-scale fire test[J]. Chinese science bulletin, 2007, 52(9): 1282-1286. DOI: 10.1007/s11434-007-0151-y
Authors:Wang Wei  Zhang HePing  Wan YuTian
Affiliation:(1) State Key Laboratory of Fire Science, University of Science and Technology of China, Hefei, 230027, China
Abstract:Lining materials are widely used in buildings to cover walls and ceilings. Combustible linings may produce a potential high fire hazard in buildings. Once ignited,it propagates fire and accelerates the enclosure fire growth. Two types of lining materials were studied during the tests:block board and plywood. The test was conducted in an ISO 9705 room,where linings were mounted on walls without the ceiling. By changing the heat output of the burner,the ventilation,etc.,the concentrations of CO2/CO of different lining materials were researched. The effect of test conditions on the production of CO2/CO of different lining materials was investigated,and useful experimental data were provided for the further development of numerical modeling to simulate enclosure fire growth lined with combusti-ble materials.
Keywords:lining  CO2/CO  room corner fire  full-scale test