Dynamic Performance of On-off Operation for a Small Scale Direct Fired Absorption Chiller |
| |
Authors: | Wang LeiEnvironment Science and Engineering College Dong Hua University Shanghai Lu ZhenEnergy and Power Institute Shanghai Jiaotong University Shanghai |
| |
Institution: | 1. Environment Science and Engineering College, Dong Hua University, Shanghai, 200051 2. Energy and Power Institute, Shanghai Jiaotong University, Shanghai, 200030 |
| |
Abstract: | A part load operation by turning the burner on and off intermittently is effective for a small scale direct fired absorption chiller. The dynamic performance of the system has been investigated. The relationship between pressure, temperature and concentration of the lithium bromide solution have been analyzed. The result obtained indicates that the pressure of the high pressure generator and the temperature of the exhausted smoke are the most sensitive parameters. It is also found that the transition time from a full load to a part load condition is quite long, and part load relative cooling capacity is almost near the intermittent running time ratio and oil consumption ratio. |
| |
Keywords: | direct fired absorption chiller part load dynamic performance |