首页 | 本学科首页   官方微博 | 高级检索  
     检索      

基于多节点模型的大空间垂直温度分布研究
引用本文:刘昊儒,黄晨,王昕.基于多节点模型的大空间垂直温度分布研究[J].上海理工大学学报,2016,38(6):563-567,575.
作者姓名:刘昊儒  黄晨  王昕
作者单位:上海理工大学 环境与建筑学院, 上海 200093,上海理工大学 环境与建筑学院, 上海 200093,上海理工大学 环境与建筑学院, 上海 200093
基金项目:国家自然科学基金资助项目(51278302)
摘    要:针对大空间下送中回气流组织室内热环境,以室内空气为研究对象,通过在垂直方向上分层建立能量平衡方程与质量平衡方程,建立多节点温度求解模型,并利用大空间缩尺模型稳态环境实验予以验证,通过4个工况验证结果可知,各空气温度的理论计算值与实验值的最大绝对误差不超过3%,平均误差为1.4%.

关 键 词:分层空调  下送中回  多节点  垂直温度分布
收稿时间:2016/8/10 0:00:00

Application of Multi-Zone Model in Calculating the Indoor Air Temperature of Large Space Buildings
LIU Haoru,HUANG Chen and WANG Xin.Application of Multi-Zone Model in Calculating the Indoor Air Temperature of Large Space Buildings[J].Journal of University of Shanghai For Science and Technology,2016,38(6):563-567,575.
Authors:LIU Haoru  HUANG Chen and WANG Xin
Institution:School of Environment and Architecture, University of Shanghai for Science and Technology, Shanghai 200093, China,School of Environment and Architecture, University of Shanghai for Science and Technology, Shanghai 200093, China and School of Environment and Architecture, University of Shanghai for Science and Technology, Shanghai 200093, China
Abstract:Focusing on the study of indoor thermal environment under the air distribution of low supply and middle return in large spaces,an energy balance equation and mass balance equation were built to analyze each module in order to get the air temperature in multi-node.Experimental verifications for the calculation results of four working conditions were carried out by using the scale model of a large space laboratory.As shown by the results,the absolute value of maximum error between theoretical and experimental values of air temperature in respective areas is 3%,and the average error is 1.4%.
Keywords:stratified air conditioning  low supply and middle return  multi-node  vertical distribution temperature
本文献已被 CNKI 等数据库收录!
点击此处可从《上海理工大学学报》浏览原始摘要信息
点击此处可从《上海理工大学学报》下载免费的PDF全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号