首页 | 本学科首页   官方微博 | 高级检索  
     检索      

XZP-210绝缘子冰闪特性与串长和布置方式的关系
引用本文:蒋兴良,王波,张志劲,胡建林,孙才新.XZP-210绝缘子冰闪特性与串长和布置方式的关系[J].重庆大学学报(自然科学版),2007,30(7):37-41.
作者姓名:蒋兴良  王波  张志劲  胡建林  孙才新
作者单位:重庆大学,电气工程学院,高电压与电工新技术教育部重点实验室,重庆,400030;重庆大学,电气工程学院,高电压与电工新技术教育部重点实验室,重庆,400030;重庆大学,电气工程学院,高电压与电工新技术教育部重点实验室,重庆,400030;重庆大学,电气工程学院,高电压与电工新技术教育部重点实验室,重庆,400030;重庆大学,电气工程学院,高电压与电工新技术教育部重点实验室,重庆,400030
摘    要:为了给高海拔覆冰地区超特高压直流输电线路外绝缘设计提供技术参考,在人工气候室模拟高海拔大气条件进行了大量覆冰试验研究,根据试验研究结果,分析了XZP-210直流绝缘子串冰闪闪络电压与串长和布置方式的关系.结果表明,在污秽度和气压较低的条件下,覆冰绝缘子串的直流闪络电压与串长的线性关系较微弱,但随着海拔高度或污秽程度的增加,其闪络电压与串长基本呈线性关系.绝缘子串的布置方式对冰闪电压有明显影响:水平布置的覆冰绝缘子串具有最高的闪络电压,V型串次之,垂直串最低;不同布置方式下,气压对水平布置的覆冰绝缘子串的影响最为严重.

关 键 词:覆冰绝缘子  直流  高海拔  串长  布置方式  闪络电压
文章编号:1000-582X(2007)07-0037-05
修稿时间:2007-03-08

Influence of Units and Assemble on DC Flashover Voltage of Iced Insulator Strings at High Altitude Districts
JIANG Xing-liang,WANG Bo,ZHANG Zhi-jin,HU Jian-lin,SUN Cai-xin.Influence of Units and Assemble on DC Flashover Voltage of Iced Insulator Strings at High Altitude Districts[J].Journal of Chongqing University(Natural Science Edition),2007,30(7):37-41.
Authors:JIANG Xing-liang  WANG Bo  ZHANG Zhi-jin  HU Jian-lin  SUN Cai-xin
Institution:Key Laboratory of High Voltage and Electrical New Technology of Ministry of Education, College of Electrical Engineering, Chongqing University, Chongqing 400030, China
Abstract:Based on artificial tests of iced DC XZP-210 insulator strings carried out in the artificial climate chamber, the authors analyze the effects of units and assemble on the DC flashover voltage of iced insulator strings at high altitude districts. The test results show that the relationship between the DC icing flashover voltage and the insulator units is seemly linear with the increase of altitude or pollution level, although the linear relation is not obvious at the low altitude or pollution level. There is influence of the assembled form on icing flashover voltages, the flashover voltage of the horizontal string of iced insulators is highest while that of the vertical string is lowest. For various assembled forms, the effects of the air pressure on the flashover voltage of the horizontal string are most obvious.
Keywords:iced insulator  DC  high altitude  string length  flashover voltage  assembled form
本文献已被 CNKI 维普 万方数据 等数据库收录!
点击此处可从《重庆大学学报(自然科学版)》浏览原始摘要信息
点击此处可从《重庆大学学报(自然科学版)》下载免费的PDF全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏