Ground-coupled heat pumps(GCHP) arecommonly used in residential heating system. To mitigatethe boreholes temperature dropping with operating time, anew exhaust-air recharging system is developed. The newrecharging system can be used in three operational modes.In this paper, a ground-coupled heat recovery ventilation(HRV) model is discussed. A thermal model is set up tofind the optimal brine flow rate and heat transfer allocationratio between exhaust and supply coils for maximum heatrecovery efficiency. Contrary to the conventional liquid-loopHRV systems, the brine temperature entering the exhaustcoil never goes blow zero(0℃), and hence defrosting isneedless in the ground-coupled HRV system. This can makethe ground-coupled HRV system over 20% more efficientthan a conventional HRV system at low outdoortemperatures.  相似文献   