Pilot protection scheme of traction network based on Teager energy operator transient energy for continuous co-phase AT power supply system
Wang Long,Cai Xiao,Gao Jingye,Cai Wang,Bi Guihong,Chen Shilong.Pilot protection scheme of traction network based on Teager energy operator transient energy for continuous co-phase AT power supply system[J].Science Technology and Engineering,2021,21(32):13728-13736.
Authors:Wang Long  Cai Xiao  Gao Jingye  Cai Wang  Bi Guihong  Chen Shilong
Institution:School of Electric Power Engineering,Kunming University of Science and Technology
Abstract:A traction network longitudinal protection scheme based on FEEMD and Teager energy operator transient energy for continuous co-phase AT power supply system is proposed. The traction substation outlet shunt capacitor and a section of contact line constitute the traction network boundary, which is found to have a strong attenuation used for high-frequency signals through analysis. Therefore, the FEEMD decomposition is used to extract the high-frequency component of the fault current, and then the Teager energy operator is used to calculate the instantaneous energy of the high-frequency component of the fault current and extract the maximum instantaneous energy at both ends. In the case of faults outside the zone, the maximum value of the instantaneous energy of the high-frequency component of the fault current is smaller; in the case of faults inside the zone, the value is larger. The difference is used to construct the protection action criterion to identify the fault location and decide whether the protection will operate. Large amount of simulation results based on PSCAD indicate that the protection scheme can accurately discriminate internal and external faults and has good resistance to transition resistance.
Keywords:continuous co-phase AT power supply system      traction network      FEEMD      Teager energy operator      pilot protection