首页 | 本学科首页   官方微博 | 高级检索  
     检索      

天然气管道站场泄漏扩散三维动态研究
引用本文:尹恒,邹庆,廖柯熹,彭善碧.天然气管道站场泄漏扩散三维动态研究[J].西南石油大学学报(自然科学版),2022,44(2):135-147.
作者姓名:尹恒  邹庆  廖柯熹  彭善碧
作者单位:1. 国家管网集团西气东输公司武汉计量研究中心, 湖北 武汉 430000;2. 油气藏地质及开发工程国家重点实验室·西南石油大学, 四川 成都 610500
摘    要:针对天然气管道站场中天然气的泄漏扩散对安全生产造成的问题,开展了天然气管道站场中天然气泄漏扩散规律研究.采用专业软件模拟的方法,使用FLACS进行模拟,设置边界条件进行求解,研究不同风速、不同风向及不同泄漏速率对天然气泄漏扩散的影响,并结合天然气行业相关标准对天然气管道站场内可燃性气体位置进行优化.研究结果表明,泄漏速...

关 键 词:天然气管道站场  泄漏  可燃性气体  探测  扩散
收稿时间:2021-06-30

Three-dimensional Dynamic Study on Leakage and Diffusion of Natural Gas Pipeline Station
YIN Heng,ZOU Qing,LIAO Kexi,PENG Shanbi.Three-dimensional Dynamic Study on Leakage and Diffusion of Natural Gas Pipeline Station[J].Journal of Southwest Petroleum University(Seience & Technology Edition),2022,44(2):135-147.
Authors:YIN Heng  ZOU Qing  LIAO Kexi  PENG Shanbi
Institution:1. Wuhan Metrology Research Center, Pipe China West East Gas Pipeline Company, Wuhan, Hubei 430000, China;2. State Key Laboratory of Oil and Gas Reservoir Geology and Exploitation, Southwest Petroleum University, Chengdu, Sichuan 610500, China
Abstract:In view of the problems caused by the leakage and diffusion of natural gas in natural gas pipeline yards on safe production, a study on the law of natural gas leakage and diffusion in natural gas pipeline yards is carried out. We adopt professional software simulation method, use FLACS software to model, set boundary conditions to solve, study the influence of different wind speeds, different wind directions and different leakage rates on natural gas leakage and diffusion, and combine the relevant standards of the natural gas industry on the combustibility of natural gas pipeline stations in optimizing the position of flammable gas. The research results show that the greater the leakage rate and the lower the wind speed, the larger the volume of combustible gas in the station area, the wider the spread of combustible gas cloud, and the higher the degree of danger. At the same time, the hazard degree of downwind leakage is less than that of other directions. It is recommended that the flammable gas detector in the receiving and dispatching tube area should be set at 1 m away from the receiving tube, and the height should be set at 2 m. This research provides important theoretical support for the safe operation of natural gas pipeline stations.
Keywords:natural gas pipeline station  leakage  flammable gas  detect  diffusion  
点击此处可从《西南石油大学学报(自然科学版)》浏览原始摘要信息
点击此处可从《西南石油大学学报(自然科学版)》下载免费的PDF全文