基于UHF技术的风电场油浸式主变压器局部放电监测与分析
引用本文:任岩,万元,胡边,龚传利.基于UHF技术的风电场油浸式主变压器局部放电监测与分析[J].上海理工大学学报,2016,38(6):540-545.
作者姓名:任岩  万元  胡边  龚传利
作者单位:中国长江三峡集团公司, 宜昌 610041;华北水利水电大学 水电学院, 郑州 450046;中国水利水电科学研究院, 北京 100038,五凌电力有限公司, 长沙 410004,五凌电力有限公司, 长沙 410004,中国水利水电科学研究院, 北京 100038
基金项目:郑州市科技攻关计划项目(X2013G0432);华北水利水电大学高层次人才科研启动项目(201316)
摘    要:为了避开风电场主变压器局部放电在线监测中存在的多种形式噪声干扰,引入了基于UHF技术的风电场油浸式变压器局部放电监测与分析方法,设计了UHF局部放电传感器及配套的硬件降频电路,仿真验证了传感器及降频电路的有效性,建立了风电场主变压器超高频局部放电监测与分析模型,研制了硬件构建方案及软件的功能框架,并利用现场实测信号对该方法进行验证.工业实践证明,UHF技术能达到避开风电场现场电磁干扰、可靠获取真实局部放电脉冲、有效诊断变压器内部故障的目的.

关 键 词:风电场  油浸式变压器  局部放电  超高频  降频电路
收稿时间:2016/3/28 0:00:00

Partial Discharge Monitoring and Analysis on the Oil Immersed Main Transformer in Wind Farms Based on UHF Technology
REN Yan,WAN Yuan,HU Bian and GONG Chuanli.Partial Discharge Monitoring and Analysis on the Oil Immersed Main Transformer in Wind Farms Based on UHF Technology[J].Journal of University of Shanghai For Science and Technology,2016,38(6):540-545.
Authors:REN Yan  WAN Yuan  HU Bian and GONG Chuanli
Institution:China Three Gorges Corporation, Yichang 610041, China;School of Water Conservancy, North China University of Water Resources and Electric Power, Zhengzhou 450046, China;China Water Conservancy and Hydropower Research Institute, Beijing 100038, China,Wuling Power Corporation LTD., Changsha 410004, China,Wuling Power Corporation LTD., Changsha 410004, China and China Water Conservancy and Hydropower Research Institute, Beijing 100038, China
Abstract:To solve the problem of multiple noises existing in wind farms which affect the partial discharge (PD) online monitoring results of oil immersed transformers,a partial discharge online monitoring and analysis method for the transformers in wind farms based on the ultra high frequency (UHF) technology was put forward and the design of the UHF PD sensor and frequency reduction circuit of its supporting hardware was made.The UHF partial discharge monitoring and analysis model for the transformers,including their hardware framework and software construction scheme was built.The method was verified by the measured signals in a certain wind farm,which proves that the method proposed can effectively avoid electromagnetic interference,obtain reliable real partial discharge pulse,and realize the fault diagnosis for transformers in wind farms.
Keywords:wind farm  oil immersed transformer  partial discharge  ultra high frequency  frequency reduction circuit