19.05 mm强化管管外冷凝换热的试验研究
引用本文:王永红,陶乐仁,黄理浩.19.05 mm强化管管外冷凝换热的试验研究[J].上海理工大学学报,2017,38(2):97-101.
作者姓名:王永红  陶乐仁  黄理浩
作者单位:特灵空调系统(中国)有限公司上海分公司, 上海 200021,上海理工大学 能源与动力工程学院, 上海 200093,上海理工大学 能源与动力工程学院, 上海 200093
基金项目:上海市重点实验室项目(13DZ2260900);上海理工大学博士启动经费项目(1D16301007)
摘    要:随着能源短缺问题的日益突出,节能环保受到人们的重视.工业上使用的换热设备,其性能的优化也受到各行业的重视.建立一套集沸腾和冷凝于一体的水平单管管外凝结换热试验装置,针对直径19.05 mm的强化管,对不同制冷剂管外凝结换热进行试验研究.通过试验分析可知:不同水流量,强化管的总体传热系数随着管入口冷却水温的上升而逐渐升高;在一定的冷却水温度下,强化管的总传热系数随着冷却水流量的增大而逐渐升高;相同工况下,R410A传热系数比R134a高出约1.28%~3.39%;凝结换热饱和温度越高,凝结传热系数越小.

关 键 词:水平单管  管外冷凝  传热系数
收稿时间:2017/1/10 0:00:00

An Experimental Study on Condensation Heat Transfer Outside the Single 19.05 mm Enhanced Tube
WANG Yonghong,TAO Leren and HUANG Lihao.An Experimental Study on Condensation Heat Transfer Outside the Single 19.05 mm Enhanced Tube[J].Journal of University of Shanghai For Science and Technology,2017,38(2):97-101.
Authors:WANG Yonghong  TAO Leren and HUANG Lihao
Institution:Trane Air Conditioning System Co., Ltd., Shanghai 200021, China,School of Energy and Power Engineering, University of Shanghai for Science and Technology, Shanghai 200093, China and School of Energy and Power Engineering, University of Shanghai for Science and Technology, Shanghai 200093, China
Abstract:With the increasing of energy crisis,energy conservation and environmental protection have attracted wide attention in the world.It is also important to use the heat transfer equipment in industry area.Here,one single horizontal tube experiment apparatus combining with boiling and condensation was built for heat transfer.Heat transfer measurements of different refrigerants on the enhanced tube with diameter of 19.05 mm were carried out.It is found that,in the case of different water flows,the overall heat transfer coefficient of the enhanced tube increased with the increasing of the temperature of inlet cooling water.And at a certain temperature of the cooling water,the overall heat transfer coefficient of the enhanced tube increased with the increasing of flows of cooling water.We also found that the heat transfer coefficient of R410A was higher than R134a by around 1.28%-3.39%,and the higher saturation condensation temperature showed the smaller heat transfer coefficient.
Keywords:horizontal tube  tube condensation  heat transfer coefficient