首页 | 本学科首页   官方微博 | 高级检索  
     检索      

对电力系统近区故障开断及高压断路器选择方法的探讨
引用本文:蒲如兰.对电力系统近区故障开断及高压断路器选择方法的探讨[J].福州大学学报(自然科学版),1990(3):53-58.
作者姓名:蒲如兰
作者单位:福州大学电气系
摘    要:本文得出两个结论:(1)表明断路器开断能力除了额定开断电流(或者额定断流容量)参数外.还必须包含有一个重要参数──开断短路时断路器触头间恢复电压参数.(2)选择断路器除按通常的方法外,还必须按开断短路时断路器触头间的恢复电压.恢复电压上升速度等参数来选择,且应符合GB1984-80 《交流高压断路器》的规定.

关 键 词:电力系统  近区故障  高压断路器

A Study on the Short-Line Fault of Power System Opening and the Means of Choosing High-Voltage Circuit-Breakers
Pu Rulan.A Study on the Short-Line Fault of Power System Opening and the Means of Choosing High-Voltage Circuit-Breakers[J].Journal of Fuzhou University(Natural Science Edition),1990(3):53-58.
Authors:Pu Rulan
Institution:Department of Electrical Engineering
Abstract:The following conclusions are reached in the paper: (1) Besides the parameter of rated interrupting current (or rated interrupting), the ability to open a breaker must include another important parameter-the rating of recovery voltage between contacts of the breaker during the short-circuit breaking. (2) Except the normal methods a breaker must be chosen according to other ratings such as recovery voltage and its rising speed and it must conform with the stipulation of GB 1984-80 "Ac high-voltage Circuit-Breaker".
Keywords:power system  short-line fault  high-voltage circuit-breaker  
本文献已被 CNKI 等数据库收录!
点击此处可从《福州大学学报(自然科学版)》浏览原始摘要信息
点击此处可从《福州大学学报(自然科学版)》下载免费的PDF全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号