Performance and Optimization for a Ground-Coupled Liquid Loop Heat Recovery Ventilation System
Authors:ZHOU Ya-su  Per FAHLEN  Torbjrn LINDHOLM
Institution:1. Department of Building Environment and Equipment Engineering,Donghua University,Shanghai201620,China
2. Department of Building Services Engineering,Chalmers University of Technology,SE-412 96,Gothenburg,Sueden
Abstract:Ground-coupled heat pumps(GCHP) arecommonly used in residential heating system. To mitigatethe boreholes temperature dropping with operating time, anew exhaust-air recharging system is developed. The newrecharging system can be used in three operational modes.In this paper, a ground-coupled heat recovery ventilation(HRV) model is discussed. A thermal model is set up tofind the optimal brine flow rate and heat transfer allocationratio between exhaust and supply coils for maximum heatrecovery efficiency. Contrary to the conventional liquid-loopHRV systems, the brine temperature entering the exhaustcoil never goes blow zero(0℃), and hence defrosting isneedless in the ground-coupled HRV system. This can makethe ground-coupled HRV system over 20% more efficientthan a conventional HRV system at low outdoortemperatures.
Keywords:a ground-coupled HRV system  thermal model  heat recovery efficiency  coils allocation ratio  brineflow rate