首页 | 本学科首页   官方微博 | 高级检索  
     检索      

基于零序电流有功分量的配电网接地故障定位
引用本文:庄伟,牟龙华.基于零序电流有功分量的配电网接地故障定位[J].同济大学学报(自然科学版),2014,42(3):0468-0473.
作者姓名:庄伟  牟龙华
作者单位:同济大学 电子与信息工程学院,上海 201804;同济大学 电子与信息工程学院,上海 201804
基金项目:上海市科学技术委员会资助(12ZR1451300),上海市教育委员会科研创新项目(11CXY12)。
摘    要:为解决数字化环境下中性点经消弧线圈并、串电阻接地系统的单相接地故障区段定位问题,对此类系统中出现单相接地故障时电网内全部线路首端保护装置可测得的零序电流进行了分析,并给出了零序电流有功分量的一般分布规律.在此基础上结合配电网故障定位的一般矩阵算法,提出了基于零序电流有功分量的配电网单相接地故障区段定位算法,并遵循IEC61850标准创建了故障定位算法的逻辑节点与逻辑设备,为小电流接地故障定位系统的设备模型建立提供了参考.基于PSCAD/EMTDC软件的配网典型故障仿真结果验证了单相接地故障定位算法的准确性.

关 键 词:补偿电网  单相接地  故障定位  零序电流有功分量  IEC61850标准
收稿时间:2013/3/20 0:00:00
修稿时间:2013/12/13 0:00:00

Active Component of Zero sequence Current based Single phase Ground Fault Location in Distribution Grid
ZHUANG Wei and MU Longhua.Active Component of Zero sequence Current based Single phase Ground Fault Location in Distribution Grid[J].Journal of Tongji University(Natural Science),2014,42(3):0468-0473.
Authors:ZHUANG Wei and MU Longhua
Abstract:In order to solve the fault section location problem of single phase to ground fault in digitalized distribution grid with arc suppression coil in parallel/series with resistance, the fault zero sequence currents measured by protection devices installed at the head ends of all sections in such distribution grid are formulated, and the general distribution regularities of the active component of zero sequence current are provided. On this basis, the zero sequence active component based single phase to ground fault section location method is proposed with the combination of general matrix algorithm for fault location in distribution grid. Moreover, the corresponding logic node and logic device is newly developed according to IEC61850, which provides reference to the device model construction of fault section location system of single phase to ground fault in compensated network. The correctness of the proposed algorithm is verified by the simulation results of several typical faults in a distribution grid model built in PSCAD/EMTDC.
Keywords:compensated network  single phase to ground fault  fault location  active component of zero sequence current  IEC61850 standard
本文献已被 CNKI 等数据库收录!
点击此处可从《同济大学学报(自然科学版)》浏览原始摘要信息
点击此处可从《同济大学学报(自然科学版)》下载免费的PDF全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏