带膨胀机CO2跨临界热泵系统的模拟计算与实验
引用本文:杨俊兰,马一太,李敏霞,刘圣春.带膨胀机CO2跨临界热泵系统的模拟计算与实验[J].天津大学学报(自然科学与工程技术版),2007,40(9):1099-1104.
作者姓名:杨俊兰  马一太  李敏霞  刘圣春
作者单位:天津大学热能研究所,天津大学热能研究所,天津大学热能研究所,天津大学热能研究所 天津300072,天津城市建设学院能源与机械工程系,天津300384,天津300072,天津300072,天津300072
基金项目:国家自然科学基金;天津市自然科学基金
摘    要:为了分析带膨胀机CO2跨临界热泵系统的性能和运行特性,对该系统建立数学模型,将模拟计算结果与实验数据进行了比较,它们的最大偏差不超过25%.然后,利用所建模型分析了冷却水进口温度和流量,以及冷冻水进口温度和流量对系统性能系数的影响.结果表明,对冷却水来说,降低进口温度和增加其流量不仅有利于提高系统的性能系数,而且能够降低最佳高压侧压力,使系统能够在更加安全高效的工况下运行.对冷冻水来说,增加冷冻水的进口温度和流量对提高系统的性能系数非常有利,而对最佳高压侧压力的影响并不是太大.通过对系统的性能进行模拟计算,可为系统的优化设计和操作运行提供理论依据和指导.

关 键 词:CO2跨临界循环  膨胀机  运行特性  模拟计算
文章编号:0493-2137(2007)09-1099-06
修稿时间:2006-12-18

Simulation and Experimental Study for Transcritical CO2 Heat Pump System with Expander
YANG Jun-lan,MA Yi-tai,LI Min-xia,LIU Sheng-chun.Simulation and Experimental Study for Transcritical CO2 Heat Pump System with Expander[J].Journal of Tianjin University(Science and Technology),2007,40(9):1099-1104.
Authors:YANG Jun-lan  MA Yi-tai  LI Min-xia  LIU Sheng-chun
Institution:1. Thermal Energy Research Institute, Tianjin University, Tianjin 300072, China; 2. Department of Energy and Mechanical Engineering, Tianjin Institute of Urban Construction, Tianjin 300384, China
Abstract:To analyze the performance and operating characteristics of the transcritical CO2 heat pump system with expander,the mathematical model for the system was developed.The performance of the system was simulated and compared with the experimental results,and the maximum error was less than 25%.Then the verified model was adopted to analyze the effect of the inlet temperature of cooling water and its mass flow rate and the inlet temperature of chilling water and its mass flow rate on the system coefficient of performance.The results show that for the cooling water,decreasing its inlet temperature and increasing its mass flow rate can not only increase the system performance but also reduce the optimal heat rejection pressure,which keeps the system operating at safe and high efficiency condition.For the chilling water,increasing its inlet temperature and mass flow rate is favorable for increasing the system performance,while the optimal heat rejection pressure is not variable.The result can provide theoretical base and instruction for the system optimization design and operation by simulating the performance of the system.
Keywords:CO2 transcritical cycle  expander  operational characteristics  simulation