首页 | 本学科首页   官方微博 | 高级检索  
     

高频电磁脉冲循环冷却水污垢处理与热阻监测系统
引用本文:杨子康,熊兰,付克勤,苗雪飞. 高频电磁脉冲循环冷却水污垢处理与热阻监测系统[J]. 重庆大学学报(自然科学版), 2014, 37(9): 26-33
作者姓名:杨子康  熊兰  付克勤  苗雪飞
作者单位:1. 重庆大学 输配电装备及系统安全与新技术国家重点实验室,重庆,400044
2. 国网重庆市电力公司璧山供电分公司,重庆,402760
3. 国网浙江省桐乡市供电公司,浙江 桐乡,314500
基金项目:中央高校基本科研业务费资助项目(CDJZR12110027)
摘    要:换热设备中循环冷却水系统在高温下容易产生污垢,不但会降低换热设备的换热效率,还会影响设备安全。通过模拟实际工业循环冷却水结构,搭建了微型循环冷却水实验平台,采用高频电磁脉冲对人工配置的碳酸钙循环冷却水溶液进行阻垢处理,观察空白实验组和不同频率的高频电磁脉冲处理组中水垢形成情况,并利用自行设计的热阻监测系统对管道热阻进行监测。实验结果表明:高频电磁脉冲对循环冷却水起到了很好的阻垢作用,主要表现为循环冷却水的电导率下降趋势和pH值上升趋势均变缓。根据模拟换热器的热阻监测结果显示,高频电磁脉冲处理组的热阻要小于空白实验组的热阻,并进一步证实了高频电磁脉冲的阻垢作用。

关 键 词:高频电磁脉冲  循环冷却水  热阻  电导率  污垢
收稿时间:2014-08-15

Dirt treatment by high-frequency electromagnetic pulse for circulating cooling water and thermal resistance monitoring system
YANG Zikang,XIONG Lan,FU Keqin and MIAO Xuefei. Dirt treatment by high-frequency electromagnetic pulse for circulating cooling water and thermal resistance monitoring system[J]. Journal of Chongqing University(Natural Science Edition), 2014, 37(9): 26-33
Authors:YANG Zikang  XIONG Lan  FU Keqin  MIAO Xuefei
Affiliation:State Key Laboratory of Power Transmission Equipment & System Security and New Technology, Chongqing University, Chongqing 400044, China,State Key Laboratory of Power Transmission Equipment & System Security and New Technology, Chongqing University, Chongqing 400045, China,Bishan Power Supply Branch of Chongqing Electric Power Corporation of State Grid Corporation, Chongqing 402760, China and Tongxiang Power Supply Branch of Zhejiang Electric Power Corporation of State Grid Corporation, Tongxiang, Zhejiang 314500, China
Abstract:The circulating cooling water systems of heat transfer equipment generates dirt easily in high temperatures. Dirt will not only reduce thermal efficiency of heat exchange equipment, but also affect the equipment safety. This paper sets up a platform of miniature water cycle based on the real structure of industrial circulating water, uses high-frequency pulse treatment method to act on calcium carbonate in circulating cooling water of manual configuration, observes the impaction of blank group and different frequencies of high frequency electromagnetic pulse groups on fouling in cooling water, and monitors the thermal resistance of cooling water by a designed thermal resistance monitoring system. The results show that the high-frequency electromagnetic pulse treatment plays a very good anti-scaling effect on circulating cooling water, because both the conductivity decline trend and pH rising trend of water becomes slow. According to the thermal resistance data of analog exchanger, thermal resistances of high frequency processing groups are less than that of blank group. Moreover, it further confirms the important role of anti-scaling for high-frequency electromagnetic pulse.
Keywords:high-frequency electromagnetic pulse  circulating cooling water  heat resistance  electric conductivity  dirt
本文献已被 万方数据 等数据库收录!
点击此处可从《重庆大学学报(自然科学版)》浏览原始摘要信息
点击此处可从《重庆大学学报(自然科学版)》下载全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏