A THEORETICAL CALCULATION OF TEMPERATURE RISE(TR) IN PIPELINE OF COOL-SUPPLY SYSTEM
摘    要:In the design of cool-supply system, the temperature rise of cooling water pipeline is usually determined by experience, but not calculated. In gcnacral, the temperature rise is 1℃ for cooling water supply pipes and 0.5℃ for return pipes. The calculated results of TR according to classical approaches of thermodynamics are smaller than the tested data. This paper has analysed the causes that affect the temperature rise in detail. The heat transfer of pipe wall and the pressure drop in pipeline are two main factors. Besides, the paper gives another five factors as follows: 1. The heat radiation from the sun to pipelines; 2. The increased heat transfer due to the water condensation around the outer wall of pipelines; 3. For the underground pipelines, the existing unstable heat transfer; 4. The effects of insulation material as well as the installed quality of insulation layer; 5.The additional cool loss produced by the accessories, such as valves, brace etc. According to the above analysis, the paper giv


A THEORETICAL CALCULATION OF TEMPERA TURE RISE (TR) IN PIPELINE OF COOL-SUPPLY SYSTEM
Wu Zhihua Lin Saoji. A THEORETICAL CALCULATION OF TEMPERA TURE RISE (TR) IN PIPELINE OF COOL-SUPPLY SYSTEM[J]. Journal of Donghua University, 1995, 0(1)
Authors:Wu Zhihua Lin Saoji
Affiliation:Wu Zhihua Lin Saoji(China Textile University)YangDonghua (East China University of Science and Technology)
Abstract:
Keywords:temperature rise  heat transfer  heat radiation  effect of insulation